Appendix B—Installation Guidelines
DG1 Series VFD MN040002EN—March 2014 www.eaton.com 47
Table 30. International Cable and Fuse Sizes—208 Vac to 240 Vac Ratings
Notes
1
Line and motor cable size is selected according to IEC60364–5–52:2009 Table B.52.4 for copper conductor with PVC insulation with a wiring condition of ambient
temperature 30°C in air and an installation method of “B2” (cables in conduit and cable trunking systems). For other wiring conditions, please refer to the
standard of IEC60364–5–52:2009 for suitable cable sizes.
2
Earthing conductor size is determined by the cross–sectional area of phase conductors according to IEC/EN61800–5–1:2007 Table 5. So if phase conductor size
is changed, earthing conductor size should also be changed accordingly.
3
If power cubes or bypass are used, a Class gG/gL fuse is recommended.
4
Available in 2015.
Frame
Size
Amp
Suffix
208V Input
Current
(CT/I
H
)
208V Input
Current
(VT/I
L
)
Current
(CT/I
H
)
at 50°C
Current
(VT/I
L
)
at 40°C
Fuse
Rating
(gG/gL)
Mains and
Motor Cable
Cu (mm
2
)
Terminal Cable Size
Main Terminal
Cu (mm
2
)
Earth Terminal
Cu (mm
2
)
FR1 3D7 3.2 4.4 3.7 4.8 6 3*1.5+1.5 0.2–6 solid or
0.2–4 stranded
0.75–6
4D8 4.4 6.1 4.8 6.6 10 3*1.5+1.5 0.2–6 solid or
0.2–4 stranded
0.75–6
6D6 6.1 7.2 6.6 7.8 16 3*1.5+1.5 0.2–6 solid or
0.2–4 stranded
0.75–6
7D8 7.2 10.2 7.8 11 16 3*1.5+1.5 0.2–6 solid or
0.2–4 stranded
0.75–6
011 10.2 11.6 11 12.5 16 3*1.5+1.5 0.2–6 solid or
0.2–4 stranded
0.75–6
FR2 012 10.2 16.3 12.5 17.5 20 3*4+4 0.5–16 4–16
017 16.2 23.2 17.5 25 32 3*4+4 0.5–16 4–16
025 23.1 29 25 31 32 3*6+6 0.5–16 4–16
FR3 031 28.7 44.2 31 48 50 3*16+16 16–35 2.5–25
048 44.4 56 48 61 63 3*16+16 16–35 2.5–25
FR4 061 56.4 64.6 61 75 80 3*25+16 16–50 6–50
075 69.4 78 75 88 100 3*35+16 16–50 6–50
088 81.4 94.3 88 114 125 3*50+25 16–50 6–50
FR5 114 105.5 129 114 143 160 3*70+35 50–185 10–120
143 132.3 157 143 170 200 3*95+50 50–185 10–120
170 157.3 189 170 211 250 3*150+95 50–185 10–120
FR6 211 195.2
4
211 261
44 4 4
261 241.4
4
261 312
44 4 4