Chapter 7—EMC Installation
42 DG1 Series VFD MN040002EN—March 2014 www.eaton.com
International EMC Protection Cable 
Requirements 
The screened cables between the variable frequency drive 
and the motor should be as short as possible.
●
Connect the screening, on both sides and across a large 
area (360° overlap), to the protective earth (PE). The power 
screening protective earth (PES) connection should be in 
the immediate proximity of the variable frequency drive 
and directly on the motor terminal box.
●
Prevent the screening from becoming unbraided, e.g., by 
pushing the opened plastic sheath over the end of the 
screening or with a rubber grommet on the end of the 
screening. As an alternative, in addition to a broad area 
cable clip, you can also twist the shielding braid at the end 
and connect to protective ground with a cable clip. To 
prevent EMC disturbance, this twisted shielding 
connection should be made as short as possible
●
Screened three- or four-wire cable is recommended for the 
motor cables. The green/yellow line of a four-wire cable 
connects the protective ground connections from the 
motor and the variable frequency drive and therefore 
minimizes the equalizing current loads on the shielding 
braid.
●
If there are additional subassemblies in a motor feeder 
(such as motor contactors, overload relays, motor reactor, 
sinusoidal filters or terminals), the shielding of the motor 
cable can be interrupted close to these subassemblies and 
connected to the mounting plate (PES) with a large area 
connection.
Free or non-screened connection cables should not be any 
longer than about 300 mm.
Table 25. 1st Environment 2nd Environment EMC Levels 
According to EN 61800-3 (2004) 
Note
1
360° earthing of the shield with cable glands in motor end needed for 
EMC Level C2. 
Table 26. Control Wiring Requirements 
Table 27. Cable Categories 
Figure 28. Cable Description 
Cable Type Category C2 Category C3 Level T
Line voltage/mains  1 1 1
Motor cable  3 
1
22
Control cable  4 4 4
Item Directive
Product IEC 61800-2
Safety UL 508C, IEC / EN 61800-5-1
EMC (at default 
settings)
Immunity: EN / IEC 61800-3, 2nd environment
Radiated emissions: EN / IEC 61800-3 (Transient Testing 
included), 1st environment
Conducted emissions: EN / IEC 61800-3
Category C1: is possible with external filter connected to 
drive. Please consult factory
Category C2: with internal filter maximum of 10m motor 
cable length 
Category C3: with internal filter maximum of 50m motor 
cable length
Cable 
Category 
Description
(All cables are rated for the specific operating voltage) 
1 Intended for fixed installation
2 Symmetrical power cable equipped with a concentric protection 
wire. 
3 Symmetrical power cable with compact low-impedance shield. 
Recommended cable transfer impedance of 1–30 MHz max. 
See figure below.
4 Screened cable equipped with compact low-impedance shield 
 
PE Conductor
and Shield
Shield
PE Conductor