Relay Output Contacts
The RPP incorporates a programmable relay output with potential free contacts for remote alarm indications.
An NC or NO contact can be used. If the state of the contact changes from the state you specify as normal, a
signal is issued. This contact can be connected to equipment at the facility (such as a light or an alarm bell) to
signal when an alarm is active on the RPP. This feature is useful if the RPP is located in a remote area where
the RPP horn may not be heard immediately.
WARNING
The relay output contacts must not be connected to any utility connected circuits. Reinforced insulation
to the utility is required. The relay output contacts have a maximum rating of 240 Vac/8A.
Figure 23. Large RPP Control Pan
Control Pan