Voltage Control 
The output voltage of the rectifiers is controlled by a number of control processes. The 
following diagram shows the various control processes, measured values and operating values 
that determine the rectifier output voltage. 
  If ac fails then any active control process stops. No control process can start until the ac supply is 
restored. 
 
 
 
 
 
Float Voltage 
Configuration 
Set the following parameter. 
 
 
Set to the voltage required to maintain optimum 
battery charge (at the nominal ambient 
temperature*) as specified by the battery 
manufacturer. The bus voltage may be adjusted 
above or below this value by the System Control 
Processes. 
  *This is the same as the Reference 
Temperature used by Temperature 
Compensation. See details on page 21. 
SC100: Menu > 
Configuration > System > 
Edit > Float Voltage 
DCTools: 
Control Processes > Voltage 
Control 
  The system voltage is limited by maximum and minimum values. The values are viewable in 
DCTools at Control Processes > Voltage Control. These values are not configurable.