SC100 Handbook 
 
Copyright © 2008-2011 Eaton Corporation.  All Rights Reserved. 
IPN 997-00012-63C    August 2011 
 
System Alarm Configuration 
The following system alarm parameters can be configured. 
 
Set to Disabled if no indication is required when the 
alarm is active. Or, set to the required alarm priority. 
See details on page 32. 
DCTools: Alarms > Alarm 
State 
If required, select a digital output (relay) that will be 
operated when the alarm is active. 
If required, select a second digital output (relay) that 
will be operated when the alarm is active. 
AC Fail 
Recognition Period 
An ac supply failure condition must be continuously 
active for this period before an AC Fail alarm is 
generated. 
DCTools: Alarms > Alarm 
Configuration 
 
Enable High Float 
Tracking 
The High Float alarm threshold will be adjusted when 
the operating voltage is changed by a voltage control 
process. 
High Float alarm is activated if the bus voltage is 
above this value. 
Enable Low Float 
Tracking 
The Low Float alarm threshold will be adjusted when 
the operating voltage is changed by a voltage control 
process. 
Low Float alarm is activated when the bus voltage is 
below this value. 
High Load alarm is activated if the bus voltage is 
above this value. 
Low Load alarm is activated if the bus voltage is below 
this value. 
Battery Fuse Fail 
Active State 
Specifies if the alarm activates from an open or closed 
contact. 
Battery 
Temperature High 
Threshold  
Battery Temperature High alarm is activated if the 
battery temperature is above this value. 
Battery 
Temperature Low 
Threshold 
Battery Temperature Low alarm is activated if the 
battery temperature is below this value. 
System Overload 
Recognition Period 
System Overload 
Threshold 
AC High alarm is activated if the ac voltage is above 
this value. 
AC Low alarm is activated if the ac voltage is below 
this value.