System Operation 
 
Copyright © 2008-2011 Eaton Corporation.  All Rights Reserved. 
IPN 997-00012-63C    August 2011 
 
Common Rectifier Configuration 
The following parameters (common to all rectifiers) can be configured. 
 
Rectifier (DC) 
Current Limit 
The output current limit of the rectifier. If set to zero, 
then the output current limit is maximum. 
SC100: Rectifiers > Rect. 
Settings 
DCTools: Rectifiers 
AC Rectifier 
Current Limit 
The input current limit of the rectifier. If set to zero, 
then the input current limit is maximum. 
Current Share ensures that the total output power of 
the power system is evenly shared between all 
rectifiers. 
Set to Enabled unless there is a specific reason to 
disable. 
Over Voltage Shut Down. A rectifier will shut down if 
its output voltage exceeds this value. 
  Recommended value is 59.2V for 48V nominal 
systems, 28.6V for 24V nominal systems. 
The ramp-up slope of the rectifier, as a percentage of 
the rectifier rated current. 
Enable Rectifier 
Shutdown 
Set to Enabled to allow rectifier shut down. 
  Load Based Rectifier Shutdown is not available 
with APR48-3G, EPR48-3G, APR24-3G and 
CR48-3G rectifiers. 
The delay from ac turn-on before the rectifier output 
turns on. 
 
  See Voltage Control on page 14 for details of the rectifier's output voltage control. 
 
 
Identify 
The rectifier's registration number does not correspond to a physical position in the dc power 
system.  
►  To identify a rectifier 
  On the SC100 keypad go to: Menu > Identity > Rectifier Identity. 
  Select a rectifier. All LEDs on the selected rectifier will flash for 60 seconds. 
  Rectifier serial numbers are printed on a label on the front of each rectifier.