Fast Charge 
After an ac supply failure, Fast Charge automatically increases the float voltage of the power 
system to recharge the batteries as quickly as possible. 
Enable Fast Charge if the site experiences frequent ac supply failures. 
  Fast Charge does NOT function during a Battery Test, Equalize or if the battery current sensor 
fails. 
  If Fast Charge is used then Battery Current Limit (BCL) should also be used. See Battery Current 
Limit on page 15 for details. 
 
 
►  To enable Fast Charge (or to stop Fast Charge manually) 
  Use the SC100 keypad to go to: Menu > Configuration > Fast Charge > Edit. 
  Or, in DCTools go to: Control Processes > Fast Charge. 
 
Information 
The following information is available about Fast Charge. 
 
Indicates if Fast Charge is Disabled, Active or Inactive. 
SC100*: Menu > Controls > 
Fast Charge 
DCTools: Control Processes 
> Fast Charge 
The current level of battery discharge. A Fast Charge 
cycle is started if this value is above the Ah Threshold. 
The maximum time to the end of the currently active 
Fast Charge. 
The adjustment to the bus voltage being applied due to 
the Fast Charge. 
*Only if Fast Charge is Enabled.