SC100 Handbook 
 
Copyright © 2008-2011 Eaton Corporation.  All Rights Reserved. 
IPN 997-00012-63C    August 2011 
 
Information 
The following information is available about Battery Characterization. 
 
Locked Out: A characterization cannot start. See Lock 
Out Remaining (below). 
Inoperative: Battery characterization data is not 
loaded, End Voltage is below the characterization end 
point, or the bus voltage or battery current is 
unavailable. 
Inactive: Battery Charge State is Floating or Charge . 
  See Battery Charge State on page 36. 
Active: The battery is being characterized. 
DCTools: Control Process > 
Battery Characterization 
The maximum time to the end of the currently active  
Battery Characterization. 
  This value is not available for the initial 
characterization. 
The time remaining until a Battery Characterization can 
be started (after the last ac power fail). Set by the 
Lockout period. 
The time to the start of the next scheduled Battery 
Characterization. 
  This value is N/A when a characterization is in 
progress or Battery Characterization is 
Disbaled. 
The adjustment to the bus voltage being applied due to 
the Battery Characterization. While a Battery 
Characterization is running, the rectifiers are turned 
down to force the battery to carry the load. 
 
 
Initial Characterization 
Use the following procedure to characterize a battery for the first time.   
  This will provide the most accurate characterization data. However, if the characterization data 
from a battery of the same size and type is available, then this can be added to the Battery 
Characterization Table manually. The following characterization is then not required. 
 
 
  It will take at least 10 hours to characterize a battery. 
  During a Battery Characterization the bus voltage will gradually reduce to the battery end 
voltage. Ensure that this will not affect the operation of any equipment connected to the dc 
power system. 
 
1  Check that all battery strings are connected and any LVD contactors are connected. 
  During a battery characterization, LVD contactor disconnection is inhibited. If any LVD 
contactor is configured to connect during a battery discharge then set it to Manual Connect to 
prevent operation during the battery characterization.