SC100 Handbook 
 
Copyright © 2008-2011 Eaton Corporation.  All Rights Reserved. 
IPN 997-00012-63C    August 2011 
 
The SC100 has two LVD control channels (LVD1 and LVD2) with three modes of operation: 
1  Normal Mode: In this mode LVD2 Slave Mode and AC Timer Mode are disabled, and LVD2 
(if Enabled) will only disconnect after LVD1. 
2  LVD2 Slave Mode: In this mode LVD2 has the same operating parameters as LVD1. 
3  AC Timer Mode: The LVD will disconnect either after the AC Timer Disconnect Delay, or 
the bus voltage drops to the Disconnect Voltage, whichever happens first. Both LVD1 and 
LVD2 can be set to AC Timer mode if required (but LVD2 will only disconnect after LVD1). 
 
The following diagram shows a typical two LVD configuration. This allows lower priority loads 
to be disconnected first (LVD1), either at a specified battery voltage or a specified time interval 
after an ac supply failure. This then prolongs battery power for the highest priority loads 
(LVD2). The battery will be disconnected when the battery voltage reaches its minimum preset 
voltage. 
 
 
 
LVD1 - low priority load 
disconnect (disconnects 
first). 
 
LVD2 - battery disconnect 
(only disconnects after 
LVD1) 
 
Connections to high 
priority loads (for example 
transmission equipment). 
 
Connections to low 
priority loads. 
 
Connection to the SC100 
system controller via the 
I/O board. 
 
 
Characterization 
If auxiliary contacts are fitted to the LVD contactor(s)*, then the LVD Characterization process 
determines the optimum operating voltages to suit the contactor(s) coil voltage. These values 
are stored in the SC100 and on the I/O board. 
An LVD Characterization Error alarm will be activated if the SC100 detects that the 
characterization values stored in the SC100 and on the I/O board are different. This happens 
when: 
  The SC100 is replaced. To clear the alarm, on the SC100 select Use IOB Values. 
  The I/O Board is replaced. To clear the alarm, on the SC100 select Use SC Values. 
  Both the SC100 and the I/O Board are replaced. In this case, re-characterize the 
contactor(s). 
  When a contactor is re-characterized it will disconnect and re-connect several times. Refer to 
Maintenance in the dc power system Installation and Operation Guide for full instructions.