EasyManua.ls Logo

Eaton SC100 - Page 68

Eaton SC100
86 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SC100 Handbook
Copyright © 2008-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-63C August 2011
Temperature Sense Inputs (IOBGP)
Number of Temperature Sense Inputs
2
One only connected as standard. Second input available
(requires additional temperature sensor).
Range
2.53V to 3.43V (-20 to +70°C [-4 to +158°F])
Resolution
< 0.01V (< 1°C [1.8°F])
Accuracy
±1°C [1.8°F] at 25°C [77°F], ±2°C [3.6°F] over rated
temperature range
Maximum Cable Length
20m (65 feet)
Connector
RJ45
Current Sense Inputs (IOBGP)
Number of Current Sense Inputs
3
Range
50 to +50mV
Resolution
<50µV
Accuracy
±0.5% at 25°C [77°F], ±1% over rated temperature
range
Connector
RJ45
Bus Voltage Sense Input (IOBGP)
Number of Bus Voltage Sense Inputs
1
Range
60V to +60V
Resolution
30mV
Accuracy
±0.5% at 25°C [77°F], ±1% over rated temperature
range
Connector
MTA156 (2-way)
Low Voltage Disconnect (IOBGP)
Number of contactor connections
2
Number of LVD channels
2
Contactor Type
Normally Open (NO) or Normally Closed (NC)*,
with or without auxiliary contacts.
* For NC contactor operation the SC100 and
IOBGP must be powered from the battery side of
the LVD.
Contactor Coil Voltage (nominal)
With auxiliary contacts: 12V, 24V or 48V
Without auxiliary contacts: Equal to nominal
system voltage
Maximum Hold-in Current
1.2A (per contactor)
Connector
MTA156 (4-way)

Table of Contents

Related product manuals