in longer cycle times. The temperature range
is adjustable from 0 to 3 °F (0.3 to 1.7 °C) in
0.5°F (0.3°C) increments.
Cool Dissipation Time The amount of time
the fan will run after the cool has been turned
o. Running the fan for a period of time allows
for any cooled air left in the ducts to circulate
throughout the home. The time is adjustable
from 0 to 900 seconds. The default value is 30
seconds.
Advanced Settings
These options customize how long each stage
will run before the next stage turns on. You may
also program when a particular stage is turned
on based on the temperature delta between the
set temperature and the current temperature.
Reverse Staging If enabled, the thermostat
will cycle down from the higher stages so
that as it approaches set point it will only be
running in stage 1. The HVAC equipment will
start in stage 1. As the stage 1 temperature
delta is exceeded, the second stage will
engage. Once the equipment has brought
the current temperature back to within the
heat or cool dierential setting, stage 2 will
disengage and stage 1 will remain running
until the set point is meet.
Stage 2 Temp Delta The minimum dierence
between the current temperature and the set
temperature that will activate the auxiliary
heat (regardless if the maximum run time of
the previous stage was reached). Options are
Auto (default) and 1 to 10 °F (0.6 to 5.6 °C).
Stage 1 Max Runtime The maximum amount
of time stage 1 will run before engaging the