UPS: MKD 700 3000 VA RT (XL) Operation and Service
Possible settings and ranges of the different parameters
Parameter
(Display)
Setting options /
Value ranges
Default
User password
[<enable><disable>]
If <enable> is set, a password must also be entered.
disable
Audio alarm
[<enable><disable>]
If <disable> is set, the acoustic signaler is then
deactivated.
enable
Output voltage
[<208V> <220V> <230V> <240V>]
230V
Output frequency
[<50Hz> <60Hz> < Auto-sensing>]
50Hz
Power strategy
[<normal><high efficiency> <converter>]
If <high efficiency> is set, the UPS operates in ECO
mode.
If <converter> is set, the UPS operates in CVF mode.
normal
DC start
[<enable><disable>]
If <enable> is set, then the cold start is possible for the
UPS.
enable
Site wiring fault
alarm
[<enable><disable>]
If <enable> is set, the UPS emits a warning signal as
soon as the phase and neutral conductor are
exchanged in the power input.
disable
Ambient
temperature
warning
[<enable><disable>]
If <enable> is set, the UPS emits a warning signal as
soon as the ambient temperature becomes too high.
enable
Automatic battery
tests period
[<0days>…<31days>]
If <0days> is set, the automatic battery test is
deactivated.
7days
Auto restart
[<enable><disable>]
If <enable> is set, the UPS starts up immediately in the
standard mode when it had been switched off after the
autonomous mode.
enable
Automatic
overload restart
[<enable><disable>]
If <enable> is set, the UPS automatically switches back
to standard mode from the bypass mode after an output
overload (the load must fall under 70% of the normal
load for this).
enable
Auto bypass
[<enable><disable>]
disable