RGF 300
15/53
Mains surveillance
Continually checks presence of the three mains phases; when one phase
is absent, it stops the appliance and switches on the “phase absent” alarm
signal LED (
AC LINE ALARM
)
EMC integrated
mains filter
According to
EN 55011
(
CEI 110-6
) Class
B
:
ISM
appliances directly connected to low voltage power mains
P
ROTECTIONS
Overvoltage protection According to
EN 61000-4-5
: overvoltage Category
II
(
4 KV
)
RGF 312 286 x 201 x 130 mm 4.0 kg
RGF 320 351 x 237 x 181 mm 5.5 kg
RGF 325 351 x 237 x 201 mm 8.0 kg
RGF 340 416 x 318 x 178 mm 11.0 kg
Dimensions and Weight
RGF 360 460 x 318 x 220 mm
17.0 kg
Materials
GW-Plast 120°C
and black anodised aluminium
Degree of protection
IP 55
Environmental pollution Strong pollution
C
ASE
Fire resistance Category
D
Case Class
I
(use of earthed protection cable)
I
NSULATION
Control circuits
4000V
between control input and mains voltage components
Working
-20 T 50
(from –20°C to + 50°C)
T
EMPERATURE
Storing
-30 T 85
(from –30°C to + 85°C)
H
UMIDITY
RH < 85%
I
NSTALLATION
Vertical wall-mounting only, with
N° 4
∅
∅∅
∅ 6
mm. holes (RGF350 with
N° 4 ∅
∅∅
∅ 8
slotted holes)
SIGNAL
Trailing cable with rated cross section
1.5 sq mm / 22-14 AWG Cu
RGF 312
Trailing cable with rated cross section
2.5 sq mm / 20-12 AWG Cu
RGF 320
Trailing cable with rated cross section
4.0 sq mm/ 24-10 AWG Cu
RGF 325
Trailing cable with rated cross section
10 sq mm / 20-6 AWG Cu
RGF 340
Trailing cable with rated cross section
10 sq mm / 20-6 AWG Cu
E
LECTRICAL
CONNECTIONS
POWER
RGF 360
Trailing cable with rated cross section
10 sq mm / 20-6 AWG Cu
89/392/EEC
Directive
73/23/EEC
Directive
(93/68)
CEI-EN 60204-1
: “ Safety of machinery”
EN 50081-2
Generic standard for industrial environment emission
EN 50082-2
Generic standard for industrial environment immunity
EN 55011
class
B
, for radiated disturbance
EN 55011
class
B
, for conducted disturbance
ENV 50140
(
IEC 801-3
) for susceptibility (on the supply)
ENV 50141
for conducted susceptibility on the signal lines
IEC 801-4
for fast transients (burst / high-frequency disturbance)
T
ECHNICAL
STANDARDS
89/336/EEC
Directive
IEC 801-2
for electrostatic discharge (
ESD
)
Table 3