10.4 Alarm delay (Ad)
The table below details the alarm delay (Ad) parameter
DISPLAY
DESCRIPTION Defines the maximum time the cooler door can be open before sounding the alarm buzzer.
CONSIDERATOINS
If disabled, the door switch is also disabled.
The ems controller does not detect door openings, therefore, the ems controller does not:
• Update the self-learning matrix for door activity.
• Manage the evaporatorfan management for door activity.
• Sound door alarms if the dooris left open.
RANGE 00 to 30 minutes
GLOBAL DEFAULT 00 (disabled)
10.5 Activity frequency (AF)
The table below details the activity frequency (AF) parameter
DISPLAY
DESCRIPTION
Defines the minimum number of door openings or motion counts to indicate an active 30
minute period in the self-learning matrix, as described below. The activity frequency applies
across all 30 minute periods within the self-learning matrix, not to individual 30 minute
periods.
CONSIDERATOINS See below
RANGE See below
GLOBAL DEFAULT 00 (low frequency)