10.17 Delay to saving (dS)
The table below details the delay to saving (dS) parameter
DISPLAY
DESCRIPTION
Defines the delay in switching to the saving mode from ready mode.
The delay starts at the end of the last active 30 minute period of the ready mode.
CONSIDERATOINS Must be set in multiples of 30 minutes.
RANGE 0 to 120 minutes (in multiples of 30 minutes)
GLOBAL DEFAULT 00 (no delay)
10.18 Defrost termination temperature (dtd)
The table below details the defrost termination temperature (dtd) parameter
DISPLAY
DESCRIPTION
Defines the temperature to end the defrost cycle.
Ending defrost cycles on temperature minimizes the duration of defrost cycles.
The temperature is measured as follows:
OFC and sub-zero coolers: the temperature is measured on the evaporator sensor.
GDC coolers: the temperature is measured on the appliance sensor.
CONSIDERATOINS
Must be set above the set point (SP) plus differential (dIF) temperature.
Must be set below IPd.
If icing up occurs,review the values of the defrost parameters.
RANGE
1 to 30ºC (33 to 86ºF)
ems75sz: -5 to 22ºC (23 to 71ºF)
GLOBAL DEFAULT
9.0ºC (48ºF)
ems75sz: 15.0ºC (59ºF)