Specifications and Reference Data
47
Specifications and Reference Data
July 2017
Reference Manual
00809-0200-4410, Rev BC
A.2 Functional specifications
A.2.1 Input voltage
10.5–30 VDC Class 2 power supply
A.2.2 Current draw
Operating current draw is based on 3.0 Watt power
consumption.
A.2.3 Radio frequency power output
from antenna
Maximum of 10 mW (10 dBm) EIRP for WL or WX antenna
types
Maximum of 40 mW (16 dBm) EIRP for WN2 high gain
option
A.2.4 Environmental
Operating temperature range
–40 to 167 °F (–40 to 75 °C)
Operating humidity range
0–100 percent relative humidity
A.2.5 EMC performance
Meets all industrial environment requirements of EN61326
and NAMUR NE-21. Maximum deviation <1% span during
EMC disturbance
(1)
.
A.2.6 Antenna options
Optional remote mount omnidirectional antenna
A.2.7 Antenna
2 dBi rubber dipole with SMA connector
SMA connection is female
A.3 Physical specifications
A.3.1 Weight
0.70 lb (0,318 kg)
A.3.2 Material of construction
Housing
Polymer
A.3.3 Rail mount
Top hat rail EN 50022
(35 mm 7.5 mm and 35 mm 15 mm)
A.4 Communication
specifications
A.4.1 Isolated RS485
2-wire communication link for Modbus RTU multidrop
connections
Baud rate: 57600, 38400, 19200, or 9600
Protocol: Modbus RTU
Wiring: Single twisted shielded pair, 18 AWG. Wiring
distance is approximately 4000 ft (1,524 m)
A.4.2 Ethernet
10/100base-TX Ethernet communication port
Protocols: Modbus TCP, OPC, EtherNet/IP, HART-IP,
https (for Web Interface)
Wiring: Cat5e shielded cable
Wiring distance 328 ft (100 m)
1. During surge event device may exceed maximum EMC deviation limit or reset;
however, device will self-recover and return to normal
operation within specified start-up time.
24
30
125
250
Current (mA)
12
10.5
Operating
Region
Voltage (VDC)