Product Certifications
54
B.6 USA
N5 U.S.A. Division
Certificate: 30349590 (FM)
Standards: FM Class 3600 – 2011,
FM Class 3611 – 2004,
FM Class 3616 – 2011,
FM Class 3810 – 2005;
Markings: NI CL 1, DIV 2, GP A, B, C, D T4; Suitable for
use in CL II, III, DIV 2, GP F, G T4; T4 (–40 °C
T
a
60 °C)
Special Condition for Safe Use (X):
1. When installed as Division 2 equipment, the Emerson
Wireless 1410 Gateway shall be mounted within a
tool-secured enclosure which meets the requirements
of ANSI/ISA 61010-1 and be capable of accepting the
applicable wiring methods per the NEC.
B.7 Canada
N6 Canada Division 2
Certificate: 2646342 (CSA)
Standards: CAN/CSA C22.2 No. 0-10,
CSA C22.2 No. 213-M1987 (R2013),
CSA C22.2 No. 61010-1 - 2012,
ANSI/ISA-12.12.01 - 2012,
UL61010-1, 3rd Edition
Markings: Suitable for CL I, DIV 2, GP A, B, C, D;
Temperature code: T4 (40 °C
T
a
70 °C)
Note
Shall be powered by a class 2 power supply.
Suitable for dry indoor locations only.
Equipment must be installed in a suitable tool accessible
enclosure subject to the end use application.
Using the Emerson Wireless 1410D Gateway and the
Emerson Wireless 781Field Link in a hazardous location
requires barriers between the two units.
B.8 Europe
N1 ATEX Type n
Certificate: Baseefa14ATEX0125X
Standards: EN 60079-0:2012, EN 60079-15:2010
Markings: II 3 G Ex nA IIC T4 Gc, T4(–40 °C
T
a
75 °C), V
MAX
= 30 Vdc
Special Conditions for Safe Use (X):
1. The equipment must be installed in an area of not
more than Pollution Degree 2 as defined in
IEC 60664-1, and in an enclosure that provides a
degree of protection of at least IP54 and meets the
relevant requirements of EN 60079-0 and
EN 60079-15.
2. External connections to the equipment must not be
inserted or removed unless either the area in which the
equipment is installed is known to be non-hazardous,
or the circuits connected have been de-energized.
3. The equipment is not capable of withstanding the 500
V electrical strength test as defined in clause 6.5.1 of
EN 60079-15: 2010. This must be taken into account
during installation.
4. When fitted, the surface resistivity of the remote
antenna is greater than 1 GΩ. To avoid electrostatic
charge build up, it must not be rubbed with a dry cloth
or cleaned with solvents.
Note
Currently not available for 1410D Gateway option
B.9 International
N7 IECEx Type n
Certificate: IECEx BAS 14.0067X
Standards: IEC 60079-0: 2011, IEC 60079-15: 2010
Markings: Ex nA IIC T4 Gc, T4(–40 °C
T
a
75 °C),
V
MAX
= 30 Vdc
Special Conditions for Safe Use (X):
1. The equipment must be installed in an area of not
more than Pollution Degree 2 as defined in
IEC 60664-1, and in an enclosure that provides a
degree of protection of at least IP54 and meets the
relevant requirements of EN 60079-0 and
EN 60079-15.
2. External connections to the equipment must not be
inserted or removed unless either the area in which the
equipment is installed is known to be nonhazardous, or
the circuits connected have been de-energized.
3. The equipment is not capable of withstanding the
500 V electrical strength test as defined in clause 6.5.1
of EN 60059-15:2010. This must be taken into account
during installation.