Menu 2 Introduction
Parameter
x.00
Parameter
description format
Keypad and
display
Serial
communications
CT Modbus
RTU
PLC Ladder
programming
CTSoft Menu 0
Advanced parameter
descriptions
46 Commander SK Advanced User Guide
www.controltechniques.com Issue Number: 9
10.3 Menu 2: Ramps
Table 10-4 Menu 2 parameters: single line descriptions
Parameter Range
Default
Setting Update Rate
Eur USA
2.01 Post ramp reference {83) ± 550 Hz
21 ms
2.02 Not used
2.03 Ramp hold OFF(0) or On(1) OFF(0) 128 ms
2.04 Ramp mode select {30} 0 to 3 1 B
2.05 Not used
2.06 S ramp enable OFF(0) or On(1) OFF(0) B
2.07 S ramp acceleration limit
0.0 to 300.0 s
2
/100 Hz
3.1 B
2.08 Standard ramp voltage
0 to DC_VOLTAGE_SET_MAX V
110V drive: 375
200V drive: 375
400V drive: 750 (Eur)
775 (USA)
575V drive: 895
690V drive: 1075
B
2.09 Not used
2.10 Acceleration rate selector 0 to 9 0 5 ms
2.11 Acceleration rate 1 {03} 0.0 to 3200.0 s/100 Hz 5.0 33.0 5 ms
2.12 Acceleration rate 2
0.0 to 3200.0 s
/100 Hz
5.0 5 ms
2.13 Acceleration rate 3
0.0 to 3200.0 s
/100 Hz
5.0 5 ms
2.14 Acceleration rate 4
0.0 to 3200.0 s
/100 Hz
5.0 5 ms
2.15 Acceleration rate 5
0.0 to 3200.0 s
/100 Hz
5.0 5 ms
2.16 Acceleration rate 6
0.0 to 3200.0 s
/100 Hz
5.0 5 ms
2.17 Acceleration rate 7
0.0 to 3200.0 s
/100 Hz
5.0 5 ms
2.18 Acceleration rate 8
0.0 to 3200.0 s
/100 Hz
5.0 5 ms
2.19 Jog acceleration rate
0.0 to 3200.0 s
/100 Hz
0.2 5 ms
2.20 Deceleration rate selector 0 to 9 0 5 ms
2.21 Deceleration rate 1 {04}
0.0 to 3200.0 s
/100 Hz
10.0 33.0 5 ms
2.22 Deceleration rate 2
0.0 to 3200.0 s
/100 Hz
10.0 5 ms
2.23 Deceleration rate 3
0.0 to 3200.0 s
/100 Hz
10.0 5 ms
2.24 Deceleration rate 4
0.0 to 3200.0 s
/100 Hz
10.0 5 ms
2.25 Deceleration rate 5
0.0 to 3200.0 s
/100 Hz
10.0 5 ms
2.26 Deceleration rate 6
0.0 to 3200.0 s
/100 Hz
10.0 5 ms
2.27 Deceleration rate 7
0.0 to 3200.0 s
/100 Hz
10.0 5 ms
2.28 Deceleration rate 8
0.0 to 3200.0 s
/100 Hz
10.0 5 ms
2.29 Jog deceleration rate
0.0 to 3200.0 s
/100 Hz
0.2 5 ms
2.30 Acceleration selected indicator
1 to 8 5 ms
2.31 Deceleration selected indicator
1 to 8 5 ms
2.32 Acceleration select bit 0 OFF(0) or On(1) OFF(0) 5 ms
2.33 Acceleration select bit 1 OFF(0) or On(1) OFF(0) 5 ms
2.34 Acceleration select bit 2 OFF(0) or On(1) OFF(0) 5 ms
2.35 Deceleration select bit 0 OFF(0) or On(1) OFF(0) 5 ms
2.36 Deceleration select bit 1 OFF(0) or On(1) OFF(0) 5 ms
2.37 Deceleration select bit 2 OFF(0) or On(1) OFF(0) 5 ms
2.38 Not used
2.39 Ramp rate units 0 to 2 1 B