Service Manual Damcos LPU: Setup new P-net LPU circuit board
SM 8000-100-01 Ed 04 February 2017
102
4. Select Password - Enter Password from the menu.
5. Enter password and press OK.
6. Select Tools - Work offline. This will set the system
online.
7. Select the LPU/valve where the P-net LPU circuit
board has been replaced.
8. Double click on the Service Channel. 9. Type in the S/N from the new P-net circuit board
and the select Store and OK.
10.Right click on the valve name and then select
Store. This will download the setting for the LPU.
11.The LPU should now work again!
Replace Circuit Board in LPU