Service Manual Damcos LPU: Troubleshooting Guide LPU
SM 8000-100-01 Ed 04 February 2017
52
Solenoid valve not working
Action: Check that solenoid valve is energized (230 V on terminals “N” and “SV”).
If coil is energized, but solenoid valve does not work, the resistance of the coil is measured (LPU-
D). The coil must have a resistance of approximate 520
for LPU-D. Due to a diode bridge resis-
tance cannot be measured for LPU-S coil. Another way to check the coil is to loosen it and try to
lift the coil when energized. If coil does not work, it is replaced.
If coil works, the valve is to be replaced. See “Replace Solenoid Valve in LPU-D” on page 107.