1592038420 XRB30-60-70-77CH EN v1.1 2021.09.15 XRB 23/38
NOTES:
- In case of any blackout, the calculated energy saving model will be reset.
- ErA can exclusively drive the light output by using the LdE parameter. When LdE=YES, the light output
status will change according to the energy saving (ES) status:
• OFF if ES is active
• ON if ES is not active
- It is always possible to override the light output status by using the frontal button. Anyway, this
modification will have a temporary impact on the lights if LdE=YES. In fact, ErA will take the control after
the next ES status change.
- ErA does not need and does not use any door switch input or motion sensor (i2F=EMt) to work.
- Be sure to place the room temperature probe in near the upper zone of the cabinet: this gives the best
results in terms of temperature variation analysis.
- The Aid parameter indicates the interval of analysis as “number of days”. The suggested values for it are
1 or 7, depending on the application.
- When Aid=1, the first day will be used to analyze the temperature behavior and to build the model to
apply to the second day. The model will be updated every day to better match the working conditions.
- When Aid=7, the first 7 days will be used to analyze the temperature behavior and to build the model to
apply to the next 7 days. The model will be updated every 7 days to better match the working conditions.
- When Aid=7, the first 7 days after power on will use a sub analysis base on 1-day model.
10.2.2 INTERACTION WITH OTHER SENSORS
The following table indicates the interaction between advanced energy saving mode (ErA=Aut) and various
digital input functions. Par. EtS, StE are not considered when ErA=Aut.