Module Setup and Calibration
4�3 Mode
1. S4 ON = Go to Default Position on loss of analog input control signal - Figure 10.
S4 OFF = Stay put on loss of analog input control signal - Figure 10.
Figure 10
2. S5 OFF and S6 OFF > Select Futronic II mode
(Electromechanical motor starter) - Figure 11.
Figure 11
3. S5 ON and S6 OFF > Select Futronic III mode
(SCR solid-state DC motor starter) - Figure 12.
Figure 12
4. S5 OFF and S6 ON > Select Futronic IV mode
(Triac solid-state (SSR) motorstarter) - Figure 13.
Figure 13
8
Section 4: Module Setup and Calibration