FB1100 Flow Computer Instruction Manual
D301752X012
November 2023
56 Service and Troubleshooting
Table 4-1. LED Descriptions
Link LED GREEN
An active wired Ethernet connection exists.
Otherwise, it is off. (FB1200/FB2200 only)
One of the IR buttons is being pressed.
Flashing YELLOW
CPU booting or CPU has not yet recognized HMI
module when HMI first powered on; goes off
when recognized.
Status LED GREEN
OK – Main power battery pack charged or not in
use.
Flashing RED
Main power battery pack low. Replace/re-charge
lead acid battery pack soon. (If FB1100 Flow
Computer with lithium battery pack– replace
battery pack.)
Flashing YELLOW
FB1100 Flow Computer with lithium battery
pack only: Unit has switched to C cell battery
internal to battery pack. Replace battery pack
soon.
Main power battery pack charging
Flashing RED
HMI firmware update in progress.
Table 4-2. Special LED Sequences Using Multiple LEDs
Link, Input, Status, and Alarm all solid RED
HMI module failed. Replace with spare
or return for repairs.
Link and Alarm alternately flash RED;
sequence repeats
CPU stuck in boot mode. Contact
technical support.
4.3 Switch and Buttons
A momentary switch and two push-buttons on the HMI module provide trouble-shooting
options for the flow computer.
EXPLOSION HAZARD: Never remove end cap(s) in a hazardous location. Removing end
cap(s) in a hazardous location could result in an explosion.