FB2100 Flow Computer Instruction Manual
D301783X012
November 2023
88 Service and Troubleshooting
Table 5-1: LED Descriptions
Link LED GREEN
An active wired Ethernet connection exists.
Otherwise it is off. (FB1200/FB2200 only)
One of the IR buttons is being pressed.
Flashing YELLOW
CPU booting or CPU has not yet recognized
HMI module when HMI first powered on;
goes off when recognized.
Status LED GREEN
OK – Main power battery pack charged or
not in use.
Flashing RED
Main power battery pack low. Replace/re-
charge lead acid battery pack soon. (If
FB1100 Flow Computer with lithium battery
pack– replace battery pack.)
Flashing YELLOW
FB1100 Flow Computer with lithium battery
pack only: Unit has switched to C cell battery
internal to battery pack. Replace battery
pack soon.
Main power battery pack charging
HMI firmware update in progress.
Table 5-2. Special LED Sequences using Multiple LEDs
Alarm all solid RED
HMI module failed. Replace with spare or return for
repairs.
Link and Alarm alternately
flash RED; sequence
repeats
CPU stuck in boot mode. Contact technical support.