FB2100 Flow Computer Instruction Manual
D301783X012
November 2023
Installation 35
Table 2-4. Typical Power Usage Low Power Mode at Room Temperature
Description
Power Usage
(mW) at 12Vdc
Base flow computer with integral multivariable DP and pressure
sensor and temperature measurement, single DO available, for a
single meter run.
Historical configuration supports maximum of:
4 averages
12 Station 1 history points (Group 4)
10 User Periodic history points (Group 1)
55
Base flow computer with integral multivariable DP and pressure
sensor and temperature measurement, 2 digital and 2 analog
channels available for a single meter run.
Historical configuration supports maximum of:
4 averages
12 Station 1 history points (Group 4)
10 User Periodic history points (Group 1)
67
Additional Load Options:
Display and backlight active
340
FBxWifi active
379
FBxWifi and display active
398
DO active (1 Hz, 50:50 duty cycle, no load)
12
PI active (10 KHz, 50:50 duty cycle, square wave)
12
Important
If you increase the number of history points/averages beyond any of the maximum limits
in
41TTable 2-441T, the flow computer cannot operate in low power mode and automatically
runs in standard power mode.
Standard Power Mode
When serial communication is active (other than to a remote 4088B MVT) the FB2100
operates in standard power mode. The unit also uses standard power mode when:
The HMI module display is ON
FBxWifi is active
Modbus Master communication is active
Power control zone enabled