36 Installation
Table 2-5. Typical Power Usage – Standard Power Mode at room temperature
Description
Usage
(mW) at
12Vdc
Usage
(mW) at
24Vdc
Base flow computer with integral multivariable DP and pressure
sensor and temperature measurement for a single meter run
240 290
Base flow computer with temperature measurement (no integral
sensor) communicating to remote 4088B (externally powered)
for a single meter run
220 268
Base flow computer with integral multivariable DP and pressure
sensor and temperature measurement, 2 digital and 2 analog
channels available for a single meter run
260 313
Base flow computer with temperature measurement, integral
static pressure sensor and pulsed input for a single meter run
276 330
Display and backlight active
FBxWifi and display active
DO active (1 Hz, 50:50 duty cycle, no load)
PI active (10 KHz, 50:50 duty cycle, square wave)
Notes on Battery Life
Battery life varies based on numerous factors including temperature, communication
usage, and various load options. To achieve the maximum battery life noted in the
product data sheet requires that you:
Limit use of the display, backlight, and FBxWifi options.
Limit communication activity.
Disable power to all I/O (except for the MV or static pressure sensor, or RTD). To do
this, click Configure > I/O Setup > I/O Configuration > Properties and select
Disable for each I/O module.