EasyManua.ls Logo

Emerson FB2100 - Analog Inputs; AI Wiring; Analog Input Characteristics

Emerson FB2100
126 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
FB2100 Flow Computer Instruction Manual
D301783X012
November 2023
I/O Configuration and Wiring 67
3.1 Analog Inputs
The FB2100 flow computer with I/O option 2 includes two on-board channels that you can
individually configure as analog inputs (AI) or analog outputs (AO).
Note
No external resistor is required for a current (mA) device. You can apply a 250 ohm
resistor using analog input configuration selections in FBxConnect.
When configured as analog inputs, the channels have the following characteristics:
Table 3-1. Analog Input Characteristics
Type
Number Supported
Characteristics
Analog Input
(AI)
0 to 2 as follows under I/O
option 2 only:
1 or 2 non-isolated channels
on CPU board (AI/AO1 and
AI/AO2) always present. You
can configure one, both, or
neither as AIs.
4 to 20 mA range (@24Vdc), or
1 to 5Vdc
Over range for calibration
purposes: 3.2 to 20.8 mA or
0.8 to 5.2 Vdc
Externally powered (current
mode only)
Factory calibrated (re-
calibration is unnecessary for
at least 3 years)
Signal conditioning
When you configure a channel
as an AI it cannot be used as
an AO
3.1.1 AI Wiring
The diagram below shows how to wire the analog input.

Table of Contents