FB2100 Flow Computer Instruction Manual
D301783X012
November 2023
I/O Configuration and Wiring 69
Type
Number Supported
Characteristics
AI/AO2) always present. You
can configure one, both, or
neither as AOs. Note: If you
configure both as AOs we
recommend you provide
isolation to avoid ground
loops which could affect
readings.
AO sinks current to system
ground
Factory calibrated (re-
calibration is unnecessary for
at least 3 years)
You can configure a fail state
so that on power up or if the
CPU fails the output drives to
0 µA
When a channel is configured
as an AO it cannot be used as
an AI
3.2.1 AO Wiring
The diagram below shows how to wire the analog output.
Figure 3-3. Analog Output (AO) Wiring [AI/AO1 & AI/AO2] (I/O Option 2)
1
Field Device
2
Power Supply 30Vdc Max
3.3 Digital Inputs
The FB2100 flow computer with I/O option 2 includes two channels that you can
individually configure as digital inputs (DI), digital outputs (DO), or pulse inputs (PI).
When configured as digital inputs, the channels have the following characteristics: