FB3000 RTU Instruction Manual
D301851X012
November 2023
56 I/O Configuration and Wiring
Figure 3-6 shows typical DO wiring using the internal loop power output.
Note
The maximum load for the loop power output is 200 mA.
Figure 3--6 Digital Output (DO) Wiring using the internal Loop Power Output
Suppression diodes typical placements
Switched load, relay coil shown