S600+ Field Upgrade Guide
 To disable termination, place the two jumpers on P9 onto the
right-most pair of pins.
Comm 9 (TB5)
Jumper P14 manages pins 1 and 2 of Comm 9 (TB5). RS-485 mode is
always active for Comm 9.
Place jumpers on the lowermost pair of pins to enable termination, or
the uppermost pair of pins to disable termination.
Comm 10 (TB5)
Jumper P13 manages pins 3 and 4 of Comm 10 (TB5). RS-485 mode
is always active for Comm 10.
Place jumpers on the lowermost pair of pins to enable termination, or
the uppermost pair of pins to disable termination.
Comm 11 (TB5)
Jumper P18 manages pins 1 and 2 of Comm 11 (TB5). RS-485 mode
is always active for Comm 11.
Place jumpers on the lowermost pair of pins to enable termination or
the uppermost pair of pins to disable termination.
Comm 12 (TB6)
Jumper P15 manages pins 1 and 2 of Comm 12 (TB6). It is active
only if you select RS-485 mode for Comm 12.
Place jumpers on the lowermost pair of pins to enable termination, or
the uppermost pair of pins to disable termination.
Jumper P17
(TB6)
Jumper P17 sets the functionality of TB6, enabling it to act either as
an RS-485 comm port or a digital input port.
Place jumpers on the leftmost upper and lower set of pins to activate
RS-485 mode. Place the jumpers on the rightmost upper and lower set
of pins to enable TB6 to act as a digital input port.
Note: This is new functionality with the S600+ CPU module.
Proceed to the next step.
10. Set Security Jumper
Jumper P3 (see Figure 7) enables or disables system security. When
the CPU module is delivered from the factory, P3 does not contain a
jumper. This disables system security, and requires you to supply a
password to change S600+ settings. Install a jumper on P3 to enable
this security feature.
Proceed to the next step.
11. Set Cold Start Jumper
Jumper P2 (see Figure 7) enables automatic warm start. As delivered
from the factory, P2 does not contain a jumper. Place a jumper on P2
to disable automatic warm start, allowing you to bypass the password
needed to access the cold start menu.
Proceed to the next step.
10 Revised Feb-11

Other manuals for Emerson FloBoss S600+

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson FloBoss S600+ and is the answer not in the manual?

Emerson FloBoss S600+ Specifications

General IconGeneral
BrandEmerson
ModelFloBoss S600+
CategoryController
LanguageEnglish

Related product manuals