Specifications
53 Liebert
®
GXT4
™
User Manual
8.0 Specifications
Table 8-1 UPS specifications
Model #
GXT4-5000RT230
GXT4-5000RT230E
GXT4-6000RT230
GXT4-6000RT230E
GXT4-10000RT230
GXT4-10000RT230E
Rating 5000VA/4000W 6000VA/4800W 10,000VA/9000W
Dimensions, mm (in)
Unit, W x D x H 430 x 574 x 217
(16.9 x 22.4 x 8.5)
430 x 581 x 261
(16.9 x 22.9 x 10.3)
Shipping, W x D x H 516 x 745 x 530
(20.3 x 29.3 x 20.9)
530 x 745 x 563
(20.9 x 29.3 x 22.2)
Weight, kg (lb)
Unit 60 (132.2) 70 (154.3)
Shipping
75 (165.4); “E” model 71 (156.5)
96 (211.6); “E” model 92
(202.8)
Input AC Parameters
Operating Frequency, Nom 50 or 60Hz (Factory Default is 50)
Factory Default VAC 230VAC
User-Configurable VAC 200/208/220/230/240VAC
(May be modified using included configuration program)
Operating Voltage Range Without
Battery Operation
176 - 280VAC
Maximum Allowable VAC 280VAC
Input Frequency Without Battery
Operation
40 - 70Hz
Input Power Connection
PD2-CE6HDWRMBS Standard
(See 1.4 - Removable Power Distribution Box)
PD2-CE10HDWRMBS
Standard
(See 1.4 - Removable
Power Distribution Box)
Output AC Parameters
AC-AC Efficiency 92% AC-AC
Factory Default VAC
230VAC
Output Connections
PD2-CE6HDWRMBS Standard
(See 1.4 - Removable Power Distribution Box)
PD2-CE10HDWRMBS
Standard
(See 1.4 - Removable
Power Distribution Box)
Frequency 50Hz or 60Hz, Nominal
Waveform Sinewave
Main Mode Overload >200% for 5 cycles; 151 - 200% for 1 seconds; 131-150% 10 seconds; 105 - 130% 1
minute
Internal Battery Charger
Charger Current, Amperes 1.3 2.6
Battery Parameters
Type Valve-regulated, non-spillable, lead acid
Quantity x V 20 x 12V
Battery Mfr. / Part #
5AH battery, CSB HR1221W or YUASA NPH5-12
9AH battery, CSB
UPS12460F2 or CSB
HR1234WF2
Backup Time See Table 8-4 - Battery run time, minutes, all models
Recharge Time (Internal Batteries) 5 hr. to 90% capacity after full discharge into 100% load