EasyManua.ls Logo

Emerson GXT4-5000RT230 - 8 Specifications

Emerson GXT4-5000RT230
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Specifications
53 Liebert
®
GXT4
User Manual
8.0 Specifications
Table 8-1 UPS specifications
Model #
GXT4-5000RT230
GXT4-5000RT230E
GXT4-6000RT230
GXT4-6000RT230E
GXT4-10000RT230
GXT4-10000RT230E
Rating 5000VA/4000W 6000VA/4800W 10,000VA/9000W
Dimensions, mm (in)
Unit, W x D x H 430 x 574 x 217
(16.9 x 22.4 x 8.5)
430 x 581 x 261
(16.9 x 22.9 x 10.3)
Shipping, W x D x H 516 x 745 x 530
(20.3 x 29.3 x 20.9)
530 x 745 x 563
(20.9 x 29.3 x 22.2)
Weight, kg (lb)
Unit 60 (132.2) 70 (154.3)
Shipping
75 (165.4); “E” model 71 (156.5)
96 (211.6); “E” model 92
(202.8)
Input AC Parameters
Operating Frequency, Nom 50 or 60Hz (Factory Default is 50)
Factory Default VAC 230VAC
User-Configurable VAC 200/208/220/230/240VAC
(May be modified using included configuration program)
Operating Voltage Range Without
Battery Operation
176 - 280VAC
Maximum Allowable VAC 280VAC
Input Frequency Without Battery
Operation
40 - 70Hz
Input Power Connection
PD2-CE6HDWRMBS Standard
(See 1.4 - Removable Power Distribution Box)
PD2-CE10HDWRMBS
Standard
(See 1.4 - Removable
Power Distribution Box)
Output AC Parameters
AC-AC Efficiency 92% AC-AC
Factory Default VAC
230VAC
Output Connections
PD2-CE6HDWRMBS Standard
(See 1.4 - Removable Power Distribution Box)
PD2-CE10HDWRMBS
Standard
(See 1.4 - Removable
Power Distribution Box)
Frequency 50Hz or 60Hz, Nominal
Waveform Sinewave
Main Mode Overload >200% for 5 cycles; 151 - 200% for 1 seconds; 131-150% 10 seconds; 105 - 130% 1
minute
Internal Battery Charger
Charger Current, Amperes 1.3 2.6
Battery Parameters
Type Valve-regulated, non-spillable, lead acid
Quantity x V 20 x 12V
Battery Mfr. / Part #
5AH battery, CSB HR1221W or YUASA NPH5-12
9AH battery, CSB
UPS12460F2 or CSB
HR1234WF2
Backup Time See Table 8-4 - Battery run time, minutes, all models
Recharge Time (Internal Batteries) 5 hr. to 90% capacity after full discharge into 100% load

Table of Contents