Specifications
Liebert
®
GXT4
™
User Manual 54
Bypass Protection Limits
Disable Bypass Operation If input voltage exceeds ±15% of the nominal voltage
Re-Enable Bypass Operation If input voltage returns to within ±10% of nominal output voltage
Disable Bypass operation When the input frequency prevents synchronous operation
Environmental
Operating Temperature, °C (°F) 0 to 40 (32 to 104) (no derating)
Storage Temperature, °C (°F) -15 to 50 (5 to 122)
Relative Humidity 0-95% non-condensing
Operating Elevation Up to 1000m (3281 ft) at 25°C (77°F) without derating
Audible Noise <55 dBA, at 1 meter from the rear <50 dBA, at 1 meter from the front or sides
Agency
Safety IEC62040-1:2008 version, GS mark
EMI/EMC/C-Tick EMC IEC/EN/AS 62040-2 2nd Ed (Cat 2 – Table 6)
ESD IEC/EN EN61000-4-2, Level 4, Criteria A
Radiated Susceptibility IEC/EN EN61000-4-3, Level 3, Criteria A
Electrical Fast Transient IEC/EN EN61000-4-4, Level 4, Criteria A
Surge Immunity IEC/EN EN61000-4-5, Level 3, Criteria A
Transportation ISTA Procedure 1E
Table 8-2 Power distribution specifications
Model Number
PD2-CE6HDWRMBS PD2-CE10HDWRMBS
Amp Rating 32 Amps 63 Amps
Input Power Connection
Single-phase (L-N-G) hard-wired, 6-10mm
2
(8-10AWG)
Output Power Connection
Single-phase (L-N-G) hard-wired, 6-10mm
2
(8-10AWG)
Includes:
Two IEC320 C19 16A/250V Sockets
Six C13 10A/250V Sockets
Manual Bypass Switch with Indicator Lamps
Four IEC320 C19 16A/250V Sockets,
Four C13 10A/250V Sockets
Manual Bypass Switch with Indicator Lamps
Input Branch Circuit
Breaker, Supplied by User
32A 63A
Table 8-1 UPS specifications (continued)
Model #
GXT4-5000RT230
GXT4-5000RT230E
GXT4-6000RT230
GXT4-6000RT230E
GXT4-10000RT230
GXT4-10000RT230E