Specifications
Liebert
®
GXT4
™
User Manual 58
8.1 Auto-Learning Battery Run Times
As batteries age, the estimated run times may become less accurate. The Liebert GXT4 is programmed to
“learn” from a full battery discharge and modify the estimated runtime for the measured battery capacity.
This can improve accuracy and compensate for aging batteries or batteries that operate at different
ambient temperatures.
The UPS will update the anticipated run time calculation only under certain conditions.
• The UPS must have a steady load that is greater than 20%.
• The UPS must be at 100% charge at the start of a battery discharge.
• The battery discharge must continue uninterrupted until the batteries reach their end-of-discharge
voltage.
If all conditions are not met, the run time calculation will not be modified.
If the configuration program is used to change the number of battery cabinets, then the values in the
battery above table will be restored. This will override any value that is Auto-Learned.
8.2 Product Warranty Registration
Registration is not required to activate the product warranty on a Liebert UPS. Registration is required to
qualify for the Product Protection Promise. To register, visit the Emerson Network Power
®
Web site to fill
out the online form at:
www.emersonnetworkpower.com/en-US/Forms/Pages/LiebertProductWarrantyRegistration.aspx
• To contact warranty support by e-mail: microups.warranty@emerson.com
8.3 Technical Support
Technical support contacts are listed on the back cover of this document. To contact Emerson Channel
Product Support:
Phone
• NORTH AMERICA: 1-800-222-5877
• OUTSIDE NORTH AMERICA: 00-800-1155-4499
E-mail
• TECHNICAL SUPPORT: liebert.upstech@emerson.com