L: cable length (in ft)
Typical power cable resistance at 68 °F (20.0 °C)
Wire gauge Resistance
14 AWG 0.0050 Ω/ft
16 AWG 0.0080 Ω/ft
18 AWG 0.0128 Ω/ft
20 AWG 0.0204 Ω/ft
2.5 mm
2
0.0136 Ω/m
1.5 mm
2
0.0228 Ω/m
1.0 mm
2
0.0340 Ω/m
0.75 mm
2
0.0460 Ω/m
0.50 mm
2
0.0680 Ω/m
2.4 1600 transmitters in Ethernet networks
Install the 1600 Ethernet transmitter in a star network using an industrial-rated shielded
Ethernet cable.
Make sure that each cable is no longer than 328 ft (100 m).
Connect the 1600 Ethernet transmitter to the host system via a LAN (Local Area
Network) and not a WAN (Wide Area Network).
Follow all network security best practices.
Planning Installation Manual
March 2022 00825-0100-1600