Cross-section of assembled cable gland with cableFigure 4-13:
A
B
C
E
D
F
G A
A. Cable
B. Sealing nut
C. Seal
D. Compression nut
E. Braided shield
F. Brass compression ring
G. Nipple
9. Remove the junction box cover and core processor end-cap.
10. At both the sensor and transmitter, connect the cable according to the following
procedure:
a. Insert the stripped end of each wire into the corresponding terminal at the
sensor and transmitter ends, matching by color (see Table 4-6). No bare wires
should remain exposed.
Note
For ELITE
®
, H-Series, T-Series, and some F-Series sensors, match the wire to the terminal
by the color identified on the inside of the sensor junction box cover.
Sensor and transmitter terminal designationsTable 4-6:
Wire color Sensor terminal Transmitter terminal Function
Black No connection 0 Drain wires
Brown 1 1 Drive +
Red 2 2 Drive –
Orange 3 3 Temperature –
Yellow 4 4 Temperature return
Green 5 5 Left pickoff +
Blue 6 6 Right pickoff +
Violet 7 7 Temperature +
Gray 8 8 Right pickoff –
Mounting and sensor wiring for 9-wire remote installations
Installation Manual 41