Tip
If Frequency Output Scale Method is set to Frequency=Flow, and Frequency Output Maximum Pulse Width is set
to a non-zero value, Micro Motion recommends setting Frequency Factor to a value below 200 Hz.
Example: Configure Frequency=Flow
You want the frequency output to report all flow rates up to 2000 kg/min.
The frequency receiving device is configured for 10 pulses/kg.
Solution:
FrequencyFactor = x 10
2000
60
333.33FrequencyFactor =
FrequencyFactor = x N
RateFactor
T
Set parameters as follows:
Rate Factor: 2000
Frequency Factor: 333.33
6.3.3 Configure Frequency Output Maximum Pulse Width
Display
Not available
ProLink II ProLink > Configuration > Frequency/Discrete Output > Frequency > Freq Pulse Width
ProLink III Device Tools > Configuration > I/O > Outputs > Frequency Output
Field Communicator Configure > Manual Setup > Inputs/Outputs > Frequency Output > FO Settings > Max Pulse Width
Overview
Frequency Output Maximum Pulse Width is used to ensure that the duration of the ON signal is
great enough for your frequency receiving device to detect.
The ON signal may be the high voltage or 0.0 V, depending on Frequency Output Polarity.
Interaction of Frequency Output Maximum Pulse Width and Frequency
Output Polarity
Table 6-6:
Polarity Pulse width
Active High
Integrate the meter with the control system
92 Micro Motion
®
Model 1700 Transmitters with Analog Outputs