Emerson Micro Motion 1700 - Configure Calculation Speed (Response Time)

Emerson Micro Motion 1700
328 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Effects of Update Rate = Special
Incompatible features and functions
Special mode is not compatible with the following features and functions:
Enhanced events. Use basic events instead.
All calibration procedures.
Zero verification.
Restoring the factory zero or the prior zero.
If required, you can switch to Normal mode, perform the desired procedures, and then
return to Special mode.
Process variable updates
Some process variables are not updated when Special mode is enabled.
Special mode and process variable updates
Table 5-1:
Always polled and updated
Updated only when the petroleum
measurement application is disa-
bled Never updated
Mass flow
Volume flow
Gas standard volume flow
Density
Temperature
Drive gain
LPO amplitude
Status [contains Event 1 and Event
2 (basic events)]
Raw tube frequency
Mass total
Volume total
Gas standard volume total
RPO amplitude
Board temperature
Core input voltage
Mass inventory
Volume inventory
Gas standard volume inventory
All other process variables and calibra-
tion data. They retain the values held
at the time you enabled Special mode.
5.4.2 Configure Calculation Speed (Response Time)
Display
Not available
ProLink II ProLink > Configuration > Device > Response Time
ProLink III Device Tools > Configuration > Process Measurement > Response > Calculation Speed
Field Communicator
Not available
Configure device options and preferences
70 Micro Motion
®
Model 1700 Transmitters with Analog Outputs