EasyManua.ls Logo

Emerson Micro Motion 1700 - Configure an Enhanced Event

Emerson Micro Motion 1700
328 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4. Set a value for Setpoint A.
5. (Optional) Configure a discrete output to switch states in response to the event
status.
6.5.2 Configure an enhanced event
Display
Not available
ProLink II ProLink > Configuration > Discrete Events
ProLink III Device Tools > Configuration > Events > Enhanced Events
Field Communicator Configure > Alert Setup > Discrete Events
Overview
An enhanced event is used to provide notification of process changes and, optionally, to
perform specific transmitter actions if the event occurs. An enhanced event occurs (is ON)
if the real-time value of a user-specified process variable moves above (HI) or below (LO) a
user-defined setpoint, or in range (IN) or out of range (OUT) with respect to two user-
defined setpoints. You can define up to five enhanced events. For each enhanced event,
you can assign one or more actions that the transmitter will perform if the enhanced event
occurs.
Procedure
1.
Select the event that you want to configure.
2. Specify Event Type.
Options Description
HI
x > A
The event occurs when the value of the assigned process variable (x) is
greater than the setpoint (Setpoint A), endpoint not included.
LO
x < A
The event occurs when the value of the assigned process variable (x) is
less than the setpoint (Setpoint A), endpoint not included.
IN
A x B
The event occurs when the value of the assigned process variable (x) is
“in range,” that is, between Setpoint A and Setpoint B, endpoints included.
OUT
x A or x B
The event occurs when the value of the assigned process variable (x) is
“out of range,” that is, less than Setpoint A or greater than Setpoint B, end-
points included.
3. Assign a process variable to the event.
4.
Set values for the required setpoints.
For HI and LO events, set Setpoint A.
Integrate the meter with the control system
Configuration and Use Manual 101

Table of Contents

Other manuals for Emerson Micro Motion 1700

Related product manuals