Options for mA Output Fault Action and mA Output Fault Level (continued)Table 6-4:
Option mA output behavior
mA Output Fault Level
None
Tracks data for the assigned process vari-
able; no fault action
Not applicable
CAUTION!
If you set mA Output Fault Action or Frequency Output Fault Action to None, be sure to set Digital
Communications Fault Action to None. If you do not, the output will not report actual process data,
and this may result in measurement errors or unintended consequences for your process.
Restriction
If you set Digital Communications Fault Action to NAN, you cannot set mA Output Fault Action or Frequency
Output Fault Action to None. If you try to do this, the transmitter will not accept the configuration.
6.3 Configure the frequency output
The frequency output is used to report a process variable. The frequency output
parameters control how the process variable is reported. Your transmitter may have zero
or one frequency output: Channel B can be configured as a frequency output or a discrete
output.
The frequency output parameters include:
•
Frequency Output Polarity
•
Frequency Output Scaling Method
•
Frequency Output Maximum Pulse Width
• Frequency Output Fault Action and Frequency Output Fault Value
Restriction
The process variable assigned to the primary mA output is automatically assigned to the frequency
output. You cannot assign a different process variable.
Important
Whenever you change a frequency output parameter, verify all other frequency output parameters
before returning the flowmeter to service. In some situations, the transmitter automatically loads a
set of stored values, and these values may not be appropriate for your application.
Integrate the meter with the control system
Configuration and Use Manual 89