Connection to transmitter terminalsFigure C-2:
A
C
D
B
A. PC
B.
Signal converter
C. 250–600
resistance
D. Transmitter, with wiring compartment and power supply compartment opened
Note
This figure shows a serial port connection. USB connections are also supported.
3. To connect from a point in the local HART loop:
a.
Attach the leads from the signal converter to any point in the loop.
b. Add resistance as necessary.
Important
HART/Bell 202 connections require a voltage drop of 1 VDC. To achieve this, add
resistance of 250–600 to the connection.
Using ProLink III with the transmitter
302 Micro Motion
®
Model 2700 Transmitters with Analog Outputs