Emerson MICRO MOTION 2700 - F.2 Power supply terminals and ground

Emerson MICRO MOTION 2700
374 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Transmitter default values and ranges (continued)Table E-1:
Type Parameter Default Range Comments
Base volume time sec
Volume flow conversion factor 1
Variable map-
ping
Primary variable Mass flow
Secondary variable Density
Tertiary variable Mass flow
Quaternary variable Volume flow
mA output 1 Primary variable Mass flow
LRV –200.00000 g/
s
URV 200.00000 g/s
AO cutoff 0.00000 g/s
AO added damping 0.00000 sec
LSL –200 g/s Read-only.
LSL is calculated based on the
sensor size and characterization
parameters.
USL 200 g/s Read only.
USL is calculated based on the
sensor size and characterization
parameters.
MinSpan 0.3 g/s Read-only.
Fault action Downscale
AO fault level – downscale 2.0 mA 1.0 – 3.6 mA
AO fault level – upscale 22 mA 21.0 – 24.0 mA
Last measured value timeout 0.00 sec
mA output 2 Secondary variable Density
LRV 0.00 g/cm3
URV 10.00 g/cm3
AO cutoff Not-A-Number
AO added damping 0.00000 sec
LSL 0.00 g/cm
3
Read-only.
LSL is calculated based on the
sensor size and characterization
parameters.
USL 10.00 g/cm
3
Read only.
USL is calculated based on the
sensor size and characterization
parameters.
MinSpan 0.05 g/cm
3
Read-only.
Default values and ranges
Configuration and Use Manual 343