3 Mounting and sensor wiring
3.1 Mounting and sensor wiring for integral-
mount transmitters
There are no separate mounting requirements for integral transmitters, and no need to
connect wiring between the transmitter and the sensor.
3.2 Mounting transmitters
There are two options available for mounting transmitters:
Mount the transmitter to a wall or flat surface.
Mount the transmitter to an instrument pole.
3.2.1
Mounting the transmitter to a wall or flat surface
Prerequisites
Micro Motion recommends 5/16-18 (8 mm–1.25) fasteners that can withstand the
process environment. Micro Motion does not supply bolts or nuts as part of the
standard offering (general purpose bolts and nuts are available as an option).
Ensure that the surface is flat and rigid, does not vibrate, or move excessively.
Confirm that you have the necessary tools, and the mounting kit shipped with the
transmitter.
Procedure
1. Attach the mounting bracket to the transmitter and tighten the screws to 80 in lbf
(9.04 N m) to 90 in lbf (10.17 N m).
Installation Manual Mounting and sensor wiring
MMI-20027478 February 2020
Installation Manual 11