A 5700 to 3100 transmitter
connections
Use this section as a reference when wiring a 5700 transmitter to a 3100 transmitter.
The following graphic sets Channel B, configured as DO1, to relay 1. If a different channel
is assigned to DO, wire any DO to any relay.
Set up the transmitter channel configuration to DO before wiring.
Use active high and internal power.
Tie the three ground pins of the 5700 together and then land on A14 of the 3100. The
ground pins are even numbers: 4, 6, and 8.
Example (see the following figure): Use relay 1 (C) and 2 (B) with Channels B and C,
then connect terminal 2 and 4 together from 5700 and land on A14.
Land each positive power terminal on C14, C16, and C18.
Example: Using the same example as above, land 1 (Channel B) on C14 for relay 1, and
3 (Channel C) on C16 for relay 2.
Use wire size 24 AWG (0,25 mm
2
) to 16 AWG (1,5 mm
2
).
Figure A-1: 5700 to 3100 - screw-type or solder-tail connector
F3
C A
IEC 127- 2
J 3
DISC
OUT 3
T5A 250V
C A
F1
C A
IEC 127- 2
J 1
J 4
MODEL 3300/3500
TERMINAL
CONNECTION
DS1
T5A 250V
K3 K2 K1
A B C
'
(
)
DISC
OUT 2
IEC 127- 2
F2 T5A 250V
J 2
DS2
DISC
OUT 1
DS3
1 2 3 4 5 6 7 8 9 10
A14
C18
C16
C14
A. Relay 3, DO 3 pins 6 and 7, C18
B. Relay 2, DO 2 pins 5 and 6, C16
C. Relay 1, DO 1 pins 3 and 4, C14
D. Channel D
E. Channel C
F. Channel B
Installation Manual 5700 to 3100 transmitter connections
MMI-20027478 February 2020
Installation Manual 55