EasyManuals Logo

Emerson Micro Motion Configuration And Use Manual

Emerson Micro Motion
212 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #156 background imageLoading...
Page #156 background image
Milliamp output problems and recommended actions (continued)Table 10-4:
Problem Possible causes Recommended actions
mA output below
4 mA
Open in wiring
Bad output circuit
Process condition below LRV
LRV and URV are not set correctly
Fault condition if Fault Action is set to Internal
Zero or Downscale
Bad mA receiving device
Check your process conditions against the
values reported by the device.
Verify the receiving device, and the wiring
between the transmitter and the receiving
device.
Check the settings of Upper Range Value and
Lower Range Value. See Section 10.17.
Check the Fault Action settings. See
Section 10.18.
Constant mA output Incorrect process variable assigned to the
output
Fault condition exists
Non-zero HART address (mA Output 1)
Output is configured for loop test mode
Verify the output variable assignments.
View and resolve any existing alert condi-
tions.
Check the HART address. If the HART ad-
dress is non-zero, you may need to change
the setting of mA Output Action (Loop Current
Mode).
Check to see if a loop test is in process (the
output is fixed).
Check HART burst mode configuration.
See Check HART burst mode.
mA output below
3.6 mA or above
21.0 ma
Incorrect process variable or units assigned
to output
Fault condition if Fault Action is set to Upscale
or Downscale
LRV and URV are not set correctly
Verify the output variable assignments.
Verify the measurement units configured
for the output.
Check the Fault Action settings. See
Section 10.18.
Check the settings of Upper Range Value and
Lower Range Value. See Section 10.17.
Check the mA output trim. See
Section 10.15.
Consistently incorrect
mA measurement
Loop problem
Output not trimmed correctly
Incorrect measurement unit configured for
process variable
Incorrect process variable configured
LRV and URV are not set correctly
Check the mA output trim. See
Section 10.15.
Verify that the measurement units are con-
figured correctly for your application.
Verify the process variable assigned to the
mA output.
Check the settings of Upper Range Value and
Lower Range Value. See Section 10.17.
mA output correct at
lower current, but in-
correct at higher cur-
rent
mA loop resistance may be set too high Verify that the mA output load resistance
is below the maximum supported load
(see the installation manual for your trans-
mitter).
Troubleshooting
150 Micro Motion
®
Fork Density Meters (FDM)

Table of Contents

Other manuals for Emerson Micro Motion

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Micro Motion and is the answer not in the manual?

Emerson Micro Motion Specifications

General IconGeneral
CategoryMeasuring Instruments
ManufacturerEmerson
BrandMicro Motion
TypeCoriolis Flow Meter
Output4-20 mA, HART, Foundation Fieldbus, Profibus, Modbus
Power Supply24 V DC
MaterialStainless Steel, Hastelloy
Process ConnectionFlanged, Threaded
CertificationsATEX, IECEx, CSA, SIL
Pressure RatingVaries by model; up to 10, 000 psi (690 bar)
Temperature RangeVaries by model; -400 to 750°F (-240 to 400°C)

Related product manuals