11
Reference Manual
00809-0300-4410, Rev BA
Configuration
January 2018
Configuration
Figure 2-6. LOI Configuration Buttons
A. Internal configuration buttons
B. External configuration buttons
Table 2-2. LOI Button Operation
2.6.3 Setting the loop to manual
Whenever sending or requesting data that would disrupt the loop or change the output of the
transmitter, set the process application loop to manual control. The Field Communicator, AMS Device
Manager, or the LOI will prompt you to set the loop to manual when necessary. The prompt is only a
reminder; acknowledging this prompt does not set the loop to manual. It is necessary to set the loop to
manual control as a separate operation.
2.7 Verify configuration
It is recommended that various configuration parameters are verified prior to installation into the
process. The various parameters are detailed out for each configuration tool. Depending on what
configuration tool(s) are available follow the steps listed relevant to each tool.
2.7.1 Field Communicator
Configuration parameters listed in Ta bl e 2 -3 are to be reviewed prior to transmitter installation. A full list
of configuration parameters that can be reviewed and configured using a Field Communicator is located
in Appendix B: Field Communicator Menu Trees and Fast Keys.
Fast key sequences for the latest DD are shown in Ta bl e 2 -3. For Fast Key sequences for legacy DD's
contact your local Emerson Representative.
Button
Left No SCROLL
Right Yes ENTER
B
A