Field Communicator Menu Trees and Fast Keys
January 2018
Reference Manual
00809-0400-4101, Rev BA
Field Communicator Menu Trees and Fast Keys
75
B.2 Fast Keys
A () indicates the basic configuration parameters. At minimum these parameters should be verified
as a part of configuration and startup.
A (7) indicates availability only in HART revision 7 mode.
Table B-1. Device Revision 9 and 10 (HART7), DD Revision 1 Fast Key Sequence
Function
Fast Key sequence
HART 7 HART 5
Alarm and Saturation Levels 2, 2, 2, 5 2, 2, 2, 5
Damping 2, 2, 1, 1, 5 2, 2, 1, 1, 5
Primary Variable 2, 2, 5, 1, 1 2, 2, 5, 1, 1
Range Values 2, 2, 2, 1 2, 2, 2, 1
Ta g 2, 2, 7, 1, 1 2, 2, 7, 1, 1
Transfer Function 2, 2, 1, 1, 6 2, 2, 1, 1, 6
Pressure Units 2, 2, 1, 1, 4 2, 2, 1, 1, 4
Date 2, 2, 7, 1, 5 2, 2, 7, 1, 4
Descriptor 2, 2, 7, 1, 6 2, 2, 7, 1, 5
Digital to Analog Trim (4 - 20 mA Output) 3, 4, 2, 1 3, 4, 2, 1
Digital Zero Trim 3, 4, 1, 3 3, 4, 1, 3
Display Configuration 2, 2, 4 2, 2, 4
LOI Password Protection 2, 2, 6, 5 2, 2, 6, 4
Loop Test 3, 5, 1 3, 5, 1
Lower Sensor Trim 3, 4, 1, 2 3, 4, 1, 2
Message 2, 2, 7, 1, 7 2, 2, 7, 1, 6
Pressure Trend 3, 3, 1 3, 3, 1
Rerange with Keypad 2, 2, 2, 1 2, 2, 2, 1
Scaled D/A Trim (4 - 20 mA / 1-5 V) Output) 3, 4, 2, 2 3, 4, 2, 2
Scaled Variable 2, 2, 3 2, 2, 3
Sensor Temperature Trend 3, 3, 3 3, 3, 3
Switch HART Revision 2, 2, 5, 2, 4 2, 2, 5, 2, 3
Upper Sensor Trim 3, 4, 1, 1 3, 4, 1, 1
7 Long Tag 2, 2, 7, 1, 2 N/A
7 Locate Device 3, 4, 5 N/A
7 Simulate Digital Signal 3, 5 N/A