59
Reference Manual
00809-0400-4101, Rev BA
Troubleshooting
January 2018
Troubleshooting
6.3 Diagnostic messages
Listed in the below sections are detailed table of the possible messages that will appear on either the
LCD/LOI display, a Field Communicator, or an AMS Device Manager system. Use the tables below to
diagnose particular status messages.
Good
Failed – fix now
Maintenance – fix soon
Advisory
Table 6-2. Status: Failed – Fix Now
Alert name
LCD display
screen
LOI screen Problem Recommended action
No Pressure
Updates
NO P
UPDATE
NO PRESS
UPDATE
There are no pressure updates
from the sensor to the electronics
1. Ensure the sensor cable connection to the
electronics is tight.
2. Replace the transmitter.
Electronics
Board Failure
FAIL
BOARD
FAIL
BOARD
A failure has been detected in the
electronics circuit board
1. Replace the pressure transmitter.
Critical
Sensor Data
Error
MEMRY
ERROR
MEMORY
ERROR
A user written parameter does not
match the expected value
1. Confirm and correct all parameters listed
in Device Information.
2. Perform a Device Reset.
3. Replace Pressure Transmitter.
Critical
Electronics
Data Error
A user written parameter does not
match the expected value
1. Confirm and correct all parameters listed
in Device Information.
2. Perform a Device Reset.
3. Replace pressure transmitter.
Sensor Failure
FAIL
SENSOR
FAIL
SENSOR
A failure has been detected in the
pressure sensor
1. Replace pressure transmitter.
Incompatible
Electronics
and Sensor
XMTR
MSMTCH
XMTR
MSMTCH
The pressure sensor is
incompatible with the attached
electronics
1. Replace the pressure transmitter.
Table 6-3. Status: Maintenance – Fix Soon
Alert name
LCD
display
screen
LOI screen Problem Recommended action
No
Tem peratu re
Updates
NO T
UPDATE
NO TEMP
UPDATE
There are no temperature
updates from the sensor to
the electronics
1. Ensure the sensor cable connection to the
electronics is tight.
2. Replace the pressure transmitter.
Pressure Out
of Limits
PRES
LIMITS
PRES OUT
LIMITS
The pressure is either above
or below the sensor limits
1. Check the transmitter pressure connection to
ensure it is not plugged or the isolating
diaphragms are not damaged.
2. Replace the pressure transmitter.