20
Reference Manual
00809-0300-4410, Rev BA
Configuration
January 2018
Configuration
Figure 2-14. Configuring Scaled Variable Using a LOI
2.11.3 Re-mapping device variables
The re-mapping function allows the transmitter primary, secondary, tertiary, and quaternary variables
(PV, 2V, 3V, and 4V) to be configured as desired. The PV can be remapped with a Field Communicator,
AMS Device Manager, or a LOI. Variables (2V, 3V, and 4V) can only be re-mapped via Field Communicator
or AMS Device Manager.
Note
The variable assigned to the primary variable drives the 4–20 mA output. This value can be selected as
Pressure or Scaled Variable. The 2, 3, and 4 variables only apply if HART burst mode is being used.
Field Communicator
AMS Device Manager
1. Right click the device and select Configure.
2. Select Manual Setup and click on the HART tab.
3. Assign Primary, secondary, tertiary, and quaternary variables under Variable Mapping.
4. Select Send.
5. Carefully read the warning and select Yes if it is safe to apply the changes.
LOI
Refer to Figure 2-15 for instructions to remap the primary variable using a LOI.
From the HOME screen, enter the Fast Key sequence
Fast Keys
2, 1, 1, 3
EXTENDED MENU
CALIBRAT
DAMPING
TRANSFER FUNCT
SCALED VARIAB
SCALED VARIAB
ASSIGN PV
TAG
ALARM SAT VALUES
PASSWORD
SIMLATE
HART REV
BACK TO MENU
EXIT MENU
SCALED VARIAB
VIEW SCALED
CONFIG SCALED
CONFIG SCALED
BACK TO MENU
EXIT MENU
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXTENDED MENU
EXIT MENU