Electrical Installations
January 2018
Electrical Installations
Field Communicator
AMS Device Manager
1. Right click the device and select Configure.
2. Under Manual Setup select the Security tab.
3. Select Lock/Unlock button under HART Lock (Software) and follow the screen prompts.
4.4.3 Configuration button lock
The configuration button lock disables all local button functionality. Changes to the transmitter
configuration from the LOI and local buttons will be rejected. Local external keys can be locked via HART
communication only.
Field Communicator
AMS Device Manager
1. Right click the device and select Configure.
2. Under Manual Setup select the Security tab.
3. Within the Configuration Buttons dropdown menu select Disabled to lock external local keys.
4. Select Send.
5. Confirm service reason and click Yes.
4.4.4 LOI password
A Local Operator Interface Password can be entered and enabled to prevent review and modification of
device configuration via the LOI. This does not prevent configuration from HART or external keys (analog
zero and span; Digital zero trim). The LOI password is a four digit code that is to be set by the user. If the
password is lost or forgotten the master password is “9307”.
The LOI password can be configured and enabled/disabled by HART communication via a Field
Communicator, AMS Device Manager, or the LOI.
Field Communicator
From the HOME screen, enter the Fast Key sequence
Device Dashboard Fast Keys
2, 2, 6, 4
From the HOME screen, enter the Fast Key sequence
Device Dashboard Fast Keys
2, 2, 6, 3
From the HOME screen, enter the Fast Key sequence
Device Dashboard Fast Keys
2, 2, 6, 5, 2