3  Configuration
The Rosemount 2410 Tank Hub is configured by using the TankMaster WinSetup
configuration program
(3)
. WinSetup is a user-friendly software package that includes basic
configuration options as well as advanced configuration and service functions.
Configuration of the Rosemount 2410 emulation function can be performed with the
WinSetup program using the FBM or a RS485 converter, depending on the tank hub
configuration. A tank hub where the secondary field bus communicates via WirelessHART
®
,
can be configured by wireless communication with an Emerson Wireless Gateway.
3.1 
Set up Modbus communication protocol
This section describes how to configure the Modbus Master protocol channel for
communication. To specify PC communication port and the standard communication
parameters, do the following:
Procedure
1. Open the Protocols folder in the TankMaster WinSetup workspace window.
2. Select the Modbus Master icon.
3. Right click the proper MBMaster icon and select Properties to configure the protocol
channel.
4. Select the Communication tab.
(3)
See the Rosemount Tank Gauging System Configuration Manual for more information on how to use the
TankMaster WinSetup software to configure the Rosemount 2410 Tank Hub.
Manual Supplement Configuration
00809-0800-2410 August2023
Emerson.com/Rosemount 13